YBD - 12 Landscape type underground box substation

YBD – 12 Landscape type underground box substation

YBD-12 landscape underground box substation combines an underground transformer (with prefabricated pit) and an outdoor advertising light box type HV/LV switchgear. The transformer has high-voltage fuse protection and can stay submerged in water for a period, widely used in airports, highways, bridges, and tunnels. The outdoor cabinet houses HV/LV distribution equipment, with its exterior serving as a customizable advertising light box. The product covers minimal space, blends with surroundings, and provides advertising value.

Product overview

YBD – 12 series landscape underground box substation mainly consists of underground transformer (including prefabricated pit) installed underground and outdoor advertising light box type high and low voltage switchgear installed on the ground. Among them, the underground transformer is a new type of distribution transformer with high – voltage fuse protection, which can be submerged in water for a period of time. It has been widely used in airports, highways, bridges, tunnels and other places in China; the interior of outdoor light box type HV/LV switchgear is outdoor HV/LV distribution cabinet, and the exterior of the box is advertising light box. We can design the content of the poster according to the surrounding environment and user requirements. The whole product covers a small area, and is beautiful and generous, not only can be highly coordinated with the surrounding environment, but also can achieve the advertising role.

Model and meaning

Model and meaning

Service condition

● Altitude: no more than 1000m;

● Ambient temperature: maximum temperature +50 ℃, minimum temperature -25℃;

● Relative humidity: daily average value is not more than 95%; the monthly average value shall not be greater than 90%. The installation slope shall not exceed 3 degrees, in place without frequent severe vibration and impact;

● The surrounding air shall be free from explosive, corrosive, combustible gas and other obvious pollution;

Note: When ordering this product beyond the above conditions, please consult with our company.

Technical parameter

● Rated voltage level: 35kV and 10kV and below

● Frequency: 50Hz

● Insulation level (see the table below)

Rated voltage of high-voltage unit kV 10
High voltage switch unit Rated frequency Hz 50
Rated current A 630
1min power frequency withstand voltage (to ground and interphase/isolating distance) kV
Lightning impulse voltage kV 75/85
Rated short-time withstand current kA/2s 20
Rated peak withstand current kA 50
Degree of protection IP67
Low voltage switch unit Rated voltage of low-voltage unit kV 0.4
Rated current of main circuit A 50~3200
Rated short-time withstand current kA/1s 30
Rated peak withstand current kA 63
Number of branch circuits Way 0~32
Degree of protection IP34
Underground transformer Rated voltage of transformer unit kV 10
Rated capacity kVA 30~1600
Power frequency withstand voltage kV 35
Lightning impulse voltage kV 95
Connection level Dyn11
Impedance voltage 4%/4.5%
Loss S11
Degree of protection IP68

Installation diagram

Installation diagramInstallation diagram

Installation diagram

Installation diagram

Confirm The Right YBD – 12 Landscape type underground box substation Configuration

Send your voltage class, current rating, cabinet type, protection scheme, destination market and quantity. Kodery will review the request against the published product range.

Request a Quote