Product Overview
Power Xpert XGIS Air switchgear combines safety, reliability, and space savings without compromising functionality. It features a cast aluminum tank-type gas chamber with superior pressure capacity, housing the breaker, disconnector, and busbar in eco-friendly gas. The cast-type busbar ensures excellent conductivity and strength. For safety, an arc protection system discharges gas through a pressure relief channel during faults. The IP4X front-accessible enclosure allows safe operations and metering device mounting from the front. This robust design delivers exceptional value for modern power distribution needs.
Technical Parameters
| Item | Item | Unit | Parameters |
|---|---|---|---|
| Rated voltage | Rated voltage | kV | 36 |
| Rated frequency | Rated frequency | Hz | 50、60 |
| Insulating medium | / | Dry air | |
| Rated short-duration power-frequency withstand voltage | Earthing | kV | 70 |
| Rated short-duration power-frequency withstand voltage | Across vacuum contact | kV | 80 |
| Rated lightning impulse withstand voltage | Earthing | kV | 170 |
| Rated lightning impulse withstand voltage | Across vacuum contact | kV | 195 |
| Rated current | Rated current | A | 1250、2500 |
| Rated short-time withstand current | Rated short-time withstand current | kA | 31.5 |
| Rated peak withstand current | Rated peak withstand current | kA | 82kA |
| Rated duration of short-circuit | Rated duration of short-circuit | s | 3 |
| Internal arc level | Internal arc level | kA/s | IAC AFLR 31.5/1 |
| Rated inflation pressure (relative,20℃ ) | Rated inflation pressure (relative,20℃ ) | MPa | 0.22 |
| Alarm pressure ( relative,20℃ ) | Alarm pressure ( relative,20℃ ) | MPa | 0.2 |
| Min. function pressure ( relative,20℃ ) | Min. function pressure ( relative,20℃ ) | MPa | 0.19 |
| Annual leak rate | Annual leak rate | %/Y | ≤0.05 |
| Protection grade | Enclosure | Enclosure | IP4X |
| Gas tank | Gas tank | IP67 |
Conditions of working environment
| Item | Parameters |
|---|---|
| Max. temperature | 40℃ |
| Altitude | ≤1000m |
| Relative humidity | Daily average≤95%, monthly average≤90% |
| Value of vapor pressure | Daily average≤2.2kPa, monthly average≤1.8kPa |
| Seismic capability | The earthquake intensity not exceeding Magnitude 8 |
| Installation site | The ambient air is not seriously polluted by corrosive or flammable gases and dust |
Outline dimension drawing of switchgear
A. Upper LV control department
B. Three-position and circuit breaker mechanism department
C. Lower LV control department
D. Busbar and Three-position department
E. Circuit breaker department
F. Cable department
| Rated voltage (kV) | Rated current (A) | w(mm) | d(mm) | h(mm) |
|---|---|---|---|---|
| 36 | 1250 | 600 | 1800 | 2400 |
| 36 | 2500 | 800 | 1800 | 2400 |