Power Xpert XGIS Air switchgear

Power Xpert XGIS Air switchgear

Power Xpert XGIS Air switchgear combines safety, reliability, and space savings without compromising functionality. It features a cast aluminum tank-type gas chamber with superior pressure capacity, housing the breaker, disconnector, and busbar in eco-friendly gas. The cast-type busbar ensures excellent conductivity and strength. For safety, an arc protection system discharges gas through a pressu

Product Overview

Power Xpert XGIS Air switchgear combines safety, reliability, and space savings without compromising functionality. It features a cast aluminum tank-type gas chamber with superior pressure capacity, housing the breaker, disconnector, and busbar in eco-friendly gas. The cast-type busbar ensures excellent conductivity and strength. For safety, an arc protection system discharges gas through a pressure relief channel during faults. The IP4X front-accessible enclosure allows safe operations and metering device mounting from the front. This robust design delivers exceptional value for modern power distribution needs.

Technical Parameters

Item Item Unit Parameters
Rated voltage Rated voltage kV 36
Rated frequency Rated frequency Hz 50、60
Insulating medium / Dry air
Rated short-duration power-frequency withstand voltage Earthing kV 70
Rated short-duration power-frequency withstand voltage Across vacuum contact kV 80
Rated lightning impulse withstand voltage Earthing kV 170
Rated lightning impulse withstand voltage Across vacuum contact kV 195
Rated current Rated current A 1250、2500
Rated short-time withstand current Rated short-time withstand current kA 31.5
Rated peak withstand current Rated peak withstand current kA 82kA
Rated duration of short-circuit Rated duration of short-circuit s 3
Internal arc level Internal arc level kA/s IAC AFLR 31.5/1
Rated inflation pressure (relative,20℃ ) Rated inflation pressure (relative,20℃ ) MPa 0.22
Alarm pressure ( relative,20℃ ) Alarm pressure ( relative,20℃ ) MPa 0.2
Min. function pressure ( relative,20℃ ) Min. function pressure ( relative,20℃ ) MPa 0.19
Annual leak rate Annual leak rate %/Y ≤0.05
Protection grade Enclosure Enclosure IP4X
Gas tank Gas tank IP67

Conditions of working environment

Item Parameters
Max. temperature 40℃
Altitude ≤1000m
Relative humidity Daily average≤95%, monthly average≤90%
Value of vapor pressure Daily average≤2.2kPa, monthly average≤1.8kPa
Seismic capability The earthquake intensity not exceeding Magnitude 8
Installation site The ambient air is not seriously polluted by corrosive or flammable gases and dust

Outline dimension drawing of switchgear

A. Upper LV control department

B. Three-position and circuit breaker mechanism department

C. Lower LV control department

D. Busbar and Three-position department

E. Circuit breaker department

F. Cable department

Rated voltage (kV) Rated current (A) w(mm) d(mm) h(mm)
36 1250 600 1800 2400
36 2500 800 1800 2400

 

Confirm The Right Power Xpert XGIS Air switchgear Configuration

Send your voltage class, current rating, cabinet type, protection scheme, destination market and quantity. Kodery will review the request against the published product range.